Searching for just a few words should be enough to get started. If you need to make more complex queries, use the tips below to guide you.
Article type: Research Article
Authors: Monikandan, A.S.; * | Agees Kumar, C.
Affiliations: Department of Electrical and Electronics Engineering, Arunachala College of Engineering for Women, Vellichanthai
Correspondence: [*] Corresponding author. A.S. Monikandan, Associate Professor, Department of Electrical and Electronics Engineering, Arunachala College of Engineering for Women, Vellichanthai. E-mail: asmonikandan123@gmail.com.
Abstract: In this research, UPQC (Unified Power Quality Conditioner) with optimized hybrid fuzzy controller based GBSSA (Gaussian Barebone Salp Swarm Algorithm) with EPLL (Enhanced Phase Locked Loop) have been proposed for power quality enhancement in power distribution networks. Using the proposed method, the difficulties in major of the power distribution system networks can be solved, related to power quality issues. GBSSA has been employed in this research, to improve solution accuracy and optimization efficiency. Given that, it is permissible to add some extra time cost to acquire a better solution, based on the Non-Free Lunch (NFL) theory, and that the time consumption of function evaluation is rather large, when addressing actual optimization problems, the extra time consumption can be overlooked to some extent. The EPLL control method improves the standard PLL, by reducing its fundamental flaw, which is the occurrence of main frequency errors, as well as double frequency errors. It controls the DC-bus voltage of unified power quality conditioners, during supply voltage and load voltage turbulences. The proposed UPQC control technique has been found to be resilient, to a variety of source and load perturbations, including unbalanced, transient distorted supply, voltage sag, unbalanced load and voltage swell. The proposed optimized GBSSA hybrid fuzzy controller with EPLL has been proven to be more effective in reducing the THD (Total Harmonic Distortion) to 3.22%. Moreover, comparative analysis with a conventional TSF-PLL has been performed with that of Takagi-Sugeno fuzzy controller and implemented using MATLAB (MATrix Laboratory).
Keywords: UPQC, enhanced PLL, GBSSA, hybrid fuzzy controller, power quality issues
DOI: 10.3233/JIFS-213263
Journal: Journal of Intelligent & Fuzzy Systems, vol. 43, no. 6, pp. 7199-7211, 2022
IOS Press, Inc.
6751 Tepper Drive
Clifton, VA 20124
USA
Tel: +1 703 830 6300
Fax: +1 703 830 2300
sales@iospress.com
For editorial issues, like the status of your submitted paper or proposals, write to editorial@iospress.nl
IOS Press
Nieuwe Hemweg 6B
1013 BG Amsterdam
The Netherlands
Tel: +31 20 688 3355
Fax: +31 20 687 0091
info@iospress.nl
For editorial issues, permissions, book requests, submissions and proceedings, contact the Amsterdam office info@iospress.nl
Inspirees International (China Office)
Ciyunsi Beili 207(CapitaLand), Bld 1, 7-901
100025, Beijing
China
Free service line: 400 661 8717
Fax: +86 10 8446 7947
china@iospress.cn
For editorial issues, like the status of your submitted paper or proposals, write to editorial@iospress.nl
如果您在出版方面需要帮助或有任何建, 件至: editorial@iospress.nl