Particle swarm optimization tuned fuzzy terminal sliding mode control for UPS inverters

Abstract

This paper proposes a particle swarm optimization algorithm tuned fuzzy terminal sliding mode control for the application of UPS inverters. Though classic sliding mode control (SMC) is insensitive to system uncertainties, it possesses an infinite system-state convergence time. For high-accuracy tracking control, a terminal sliding mode control (TSMC) is developed to provide a finite system-state convergence time. However, difficult estimation occurs in TSMC, and incurs high UPS inverter voltage harmonics and slow dynamic response. To obtain high-quality UPS inverter output voltage, a fuzzy logic (FL) with a computationally simple and practically easy estimator is integrated into TSMC to resolve system uncertainties. Simultaneously, the particle swarm optimization (PSO) algorithm is applied to optimally tune the control gains of the TSMC with a fuzzy estimator. Results indicate that the presented combination of PSO, FL and TSMC yields a closed-loop UPS inverter with good performance under various loading conditions. Simulation and experimental results indicate that the proposed control can achieve low total harmonic distortion (THD) under nonlinear loading conditions and fast dynamic response under transient loading conditions.

1Introduction

Uninterruptible power supply (UPS) has been widely applied to provide emergency power to critical loads including safe lighting, telecommunication centers and life support equipment in hospitals that cannot afford utility failures [2]. In UPS systems, the overall performance is dependent upon the static inverter-filter arrangement, which is used to convert DC voltage to a sinusoidal AC output. A primary concern of a UPS inverter is to determine an effective controller which is able to achieve accurate tracking of the desired sinewave command. Accurate tracking for a UPS inverter should meet the following requirements: 1) perfect sinusoidal voltage waveform, even under nonlinear loading; 2) fast transient response under sudden load changes; 3) a steady-state error of approximately zero. Owing to the simple structure and easy design, a PID control is typically used as the control method for the inverter. However, a PID controller cannot achieve satisfactory performance when the controlled plant experiences highly nonlinear loading [5, 6].Several control methods have been employed, such as H-infinity control, repetitive control, and multi-loop control, but they are difficult to realize, and their algorithms are extremely complex [4, 7, 11]. Sliding mode control (SMC) is intrinsically robust against system uncertainties [15]. The SMC has been presented as a good alternative for UPS inverter design, but a linear sliding surface is employed and the system trajectory has an infinite system-state convergence time [12, 13]. Recently, a terminal sliding mode control (TSMC) with a nonlinear sliding-surface has been developed and applied to many fields. Compared to linear sliding-surface-based control, the TSMC can force the system tracking error to converge to zero in finite time, and thus achieve a high-accuracy tracking control [9, 14]. This paper introduces such a control which possesses a finite system-state convergence time mechanism to overcome the disadvantages of classic SMC with an infinite system-state convergence time for special application to UPS inverters. However, the estimation of system uncertainties is a difficult problem in TSMC systems. Such problems will yield high THD, nonzero steady-state errors, and low dynamic responses in the terminal sliding mode controlled UPS inverter. Fuzzy logic (FL) controllers have been applied to a wide range of applications in various fields. FL has been further developed for power conversion applications, since its operation principle does not require precise knowledge of the load parameters [1, 3]. Hence, the estimation of system uncertainties can be accomplished by FL. The particle swarm optimization (PSO) algorithm is also an excellent evolutionary algorithm, and has been widely applied to many areas of science and engineering [8, 10]. To enhance the performance of UPS inverters, the PSO is used to optimally tune control gains of the TSMC with the fuzzy estimator. By combining PSO, FL, and TSMC, the presented system will easily achieve finite system-state convergence time, a zero steady-state error, fast dynamic response, and prevent a low THD under various loading conditions. Simulation and experimental results are presented to illustrate the good performance of the proposed controlled UPS inverter.

2Mathematical modeling of UPS inverter

As shown in Fig. 1, the output voltage v o of the UPS inverter can be forced to track a sinusoidal reference voltage, v d by applying the proposed control.

As shown in Fig. 1, two equations can be obtained by the use of the KVL and KCL:

(1)
iL=ic+io=Cdvodt+voR
(2)
LdiLdt+vo=vi

Substituting Equations (1) into (2) yields thefollowing:

(3)
d2vodt2+1RCdvodt+1LCvo=1LCvi

Let x 1 = v o , x2=ẋ1=v̇o, ẋ2=ẍ1=v̈o and u = v i . Then, the matrix equation can beexpressed as:

(4)
[ẋ1ẋ2]=[01-1LC-1RC][x1x2]+[01LC]u

Suppose the desired output voltage is x d  = v d , and a state variable xe=[xe1xe2]T related to the tracking error is expressed by new state variables asfollows:

(5)
xe1=x1-xd=vo-vdxe2=ẋe1=ẋ1-ẋd=vȯ-vḋẍe2=-1LCxe1-1RCxe2+1LCu-1LCvd-1RCvḋ-vd̈

Thus, the error state matrix can be obtained as

(6)
[ẋe1ẋe2]=[01-a1-a2][xe1xe2]+[0a1]u+[0-a1vd-a2vḋ-vd̈]w
where a 1 indicates 1/LC, a 2 is 1/RC, and w denotes the interference. Thus, our purpose is to design a control law u. Once the u is accurately designed, the output of the UPS inberter will remain constant at the desired v d .

3Control design

For the sake of brevity, system (6) is redefined as follows:

(7)
ė1=e2ė2=f(e1,e2)+b(e1,e2)u(t)
where e 1 and e 2 represent the system error states, f (e 1, e 2) and b (e 1, e 2) are nonlinear functions of e 1 and e 2, and u (t) is the control input.

The finite-time convergent sliding function is designed as follows:

(8)
s=σ̇0+β1σ0γ1
where σ 0 = e 1 and β 1 is constant.

From Equation (8):

(9)
ṡ=σ̈0+β1γ1σ0γ1-1σ̇0=-i=12aiei+bu-w(t)+β1γ1σ0γ1-1σ̇0

Define

(10)
ai=ai0+Δai,i=1,2b=b0+Δbw(t)=a1vd+a2v̇d+v̈d
where a i0 denotes the nominal value of a i , b 0 represents the nominal value of b, Δa i indicates the variation of a i , and w (t) is the interference.

For system (6), the control law u can be expressed as follows:

(11)
u=ue+uft
where the equivalent control term u e is valid only on the sliding surface, and is defined as follows:
(12)
ṡ|u=ue,a1=a10,a2=a20,b=b0,w(t)=0=0
(13)
ue=(i=12ai0ei-β1γ1σ0γ1-1σ̇0)/b0

While the system dynamics are in sliding action,s = 0:

(14)
σ̇0=-β1σ0γ1

Substituting Equations (14) into (13) yields the following:

(15)
ue=(i=12ai0ei+β12γ1σ02γ1-1)/b0

Let

(16)
uft=i=12φiei+i=12ψiσ02γ1-1+N
where the u ft guarantees the existence of the finite-time sliding mode, and is used to eliminate systemuncertainties.

The condition for the existence of a sliding motion is, sṡ<0 as follows:

(17)
sṡ|u=ue+uft={-i=12Δaiei-Δa2e2+[Δbb0(i=12ai0ei)]+[b(i=12φiei)]+(bψ1-Δbb0β12γ1)σ02γ1-1+(-β12γ1σ02γ1-1+bψ2σ02γ1-1)+[bN-w(t)]}s<0

The conditions φ i , ψ i and N to satisfy Equation (17) can next be obtained. Notice that w (t) in Equation (17) is an interference and in practice should be rewritten as w (k), where k denotes the sample interval. Because w (k) is generally uncertain, the control in this form cannot be implemented and must beestimated.

Therefore, define the uncertainty estimation error w˜e(k) as follows:

(18)
w˜e(k)=w(k)-wˆ(k)

Then, an algorithm is expressed as:

(19)
wˆ(k)=wˆ(k-1)+β(wˆ(k-1)-wˆ(k-2))+w˜e(k-1)+β(w˜e(k-1)-w˜e(k-2))
where wˆ(k-1) is the estimated value of w (k - 1); the subscript indicates (k - 1) and (k - 2) representing the (k - 1)th and (k - 2)th sampling intervals, respectively; and |β| ≤ 1 is an adjustable parameter.

The FL is used to tune the β in Equation (19), and the fuzzy rule can be expressed as a two-input single-output system as follows:

(20)
IFw˜e(k-1)isW˜andΔw˜e(k-1)isΔW˜THENβisbeta
where W˜, ΔW˜, and beta are the fuzzy sets of w˜e(k-1), Δw˜e(k-1), and β, respectively.

The w˜e(k-1) and Δw˜e(k-1) can be easily obtained according to the following processes.

The incremental change of w˜e(k-1) is defined as follows:

(21)
Δw˜e(k-1)=w˜e(k-1)-w˜e(k-2)

From Equations (18) through (21), when the parameter β is well tuned, the w˜e(k-1) and Δw˜e(k-1) will be forced to zero and the w˜e(k) will tend toward zero. Thus, the system dynamics of system (6) will be insensitive to system perturbations, and the closed-loop system can stabilize asymptotically. The resulting fuzzy rule base designed with a two-dimensional phase plane for tuning β is displayed in Table 1.

Though the control gains can be tuned by the use of φ i , ψ i and N, thus achieving finite system-state convergence time, Equation (16) implies that the sine function across the surface s, and therefore chatter phenomenon, exists. Thus, to eliminate the chatter, the PSO algorithm represented in Equations (22) and (23) is used to optimally tune the control gains of the fuzzy TSMC. Equations (22) and (23) indicate the evolution models of a particle; then, the speed and position of each particle can be updated when moving toward a destination.

(22)
Vi+1=c0Vi+c1λ1(Xipbest-Xi)+c2λ2(Xigbest-Xi)
(23)
Xi+1=Xi+Vi+1
where c 0, c 1 and c 2 denote variables, λ 1 and λ 2 are random numbers, V i represents the present velocity, X i is the present position, Xipbest shows the best localized position, and Xigbest is the best global position. The operation of the PSO algorithm is described as follows. First, define the number of particles, and initialize their speeds and positions. Then, calculate the fitness of each particle according to F=k=1M|vo-vd|. For each particle, compare its fitness with its present best fitness. When the former is better than the latter, its present best fitness and best position are updated by its fitness and present position, respectively. Similarly, for each particle, compare its fitness with the global best fitness of the swarm. When the former is better than the latter, the global best fitness and global best position are updated by the former and the best position of the compared particle, respectively. Then, update the position and speed of each particle according to Equations (22) and (23). Finally, repeat this procedure until the terminal condition is completed.

4Simulation and experimental results

The system parameters are listed as follows: DC source voltage, V DC  = 220 V; switching frequency, f s  = 18 kHz; output voltage and frequency, v o  = 110 Vrms, f = 60 Hz; full resistive load, R = 12 Ω; diode bridge rectifier load (electrolytic capacitor: 200μF and load resistor: 55 Ω); filter inductor, L = 1.2 mH; filter capacitor, C = 10 μF. Figure 2(a) and (b) depict the simulated output voltage and the load current obtained using the proposed control and the classic SMC, respectively, under TRIAC load (from no load to full load) with a firing angle of 90° each half cycle. As shown by the figures, the proposed control indicates a smaller voltage drop and a fast recovery of the steady-state response (% THD of the output voltage equals 1.21%), as compared to the classic SMC (% THD of the output voltage equals 2.62%). The performance of the inverter with the proposed control under rectifier load is reported. Figure 2(c) indicates that the simulated output voltage waveform is nearly sinusoidal and has very small distortion (% THD of the output voltage equals 1.30%), which exceeds the industrial standard of 5% . Compared to the proposed control, the simulatedwaveforms obtained using the classic SMC under a rectifier load, are reported in Fig. 2(d), with a % THD of 5.66% ; note that the output voltage distortion is high. Additionally, experimental waveforms under TRIAC load are investigated. Figure 3(a) shows the experimental waveform with the proposed control under TRIAC load (from no load to full load) with a firing angle of 90° each half cycle. Figure 3(b) shows the experimental waveform with the classic SMC under the same load condition. Results indicate that the proposed control provides better compensation of output voltage waveform (i.e., a smaller voltage drop and faster recovery time), particularly at the firing angle (% THD of the output voltage equals 1.28%), as compared to the classic SMC (% THD of the output voltage equals 2.94%). Figure 3(c) and (d) show the experimental output voltage and the load current waveforms of the UPS inverter controlled by the proposed control and the classic SMC under rectifier load, consisting of a full wave rectified with a parallel resistor and capacitor filter. As shown in Fig. 3(c), only a slight distortion (% THD of the output voltage equals 1.36%) occurs in the output voltage when the current rises abruptly. In contrast to the proposed control, the experimental output-voltage waveform obtained using the classic SMC exhibits a high % THD of 5.87% . Indeed, the proposed control decreases the high THD, reduces the steady-state error, and quickly converges to the origin.

5Conclusions

By combining PSO, FL, and TSMC, the presented system has improved the steady-state and dynamic response of the UPS inverter. The TSMC can resolve the classic SMC problem, but the difficult estimation of system uncertainties still exists in TSMC. Such difficulty may cause high voltage harmonics, and slow transient response. The PSO algorithm is used to optimally tune the control gains of the fuzzy TSMC, thus obtaining robust UPS inverter performance. Simulation and experimental results show that THD and dynamic response results from a UPS inverter under the proposed system exceed the results achieved under the classic SMC system with both linear and nonlinear loading.

Acknowledgments

This work was supported by the Ministry of Science and Technology of Taiwan, R.O.C., under contract number MOST104-2221-E-214-011.

References

1 

Chikh A, Chandra A (2015) An optimal maximum power point tracking algorithm for PV systems with climatic parameters estimation IEEE Trans on Sustainable Energy 6: 2 644 652

2 

Wilamowski BM, Irwin JD (2011) Power electronics and motor drives CRC Press Boca Raton, FL, USA

3 

Radim B, George JK (2011) Concepts and fuzzy logic Cambridge, Massachusetts, London, England MIT Press

4 

Zhang B, Zhou KL, Wang DW (2014) Multirate repetitive control for PWM DC/AC converters IEEE Trans on Industrial Electronics 61: 6 2883 2890

5 

Shin HB, Park JG (2012) Anti-windup PID controller With integral state predictor for variable-Speed motor drives IEEE Trans on Industrial Electronics 59: 3 1509 1516

6 

Rasoanarivo I, Sargos F (2013) Multi-objective analysis for designing and controlling micro-grids under multi-control with PID, MHCC and FOPID controllers Proc IEEE Int Conf Industry Applications Society Annual Meeting 1 8

7 

He J, Li YW (2012) Generalized closed-loop control schemes with embedded virtual impedances for voltage source converters with LC or LCL filters IEEE Trans on Power Electronics 27: 4 1850 1861

8 

Parsopoulos KE, Vrahatis MN (2010) Particle swarm optimization and intelligence: Advances and applications, information science reference Hershey, PA, USA

9 

Lu KF, Xia YQ (2013) Finite-time fault-tolerant control for rigid spacecraft with actuator saturations IET Proceedings-Control Theory and Applications 7: 11 1529 1539

10 

Ishaque K, Salam Z (2013) A deterministic particle swarm optimization maximum power point tracker for photovoltaic system under partial shading condition IEEE Trans on Industrial Electronics 60: 8 3195 3206

11 

Howlader M, Urasaki N, Yona A, Senjyu T, Saber AY (2013) Design and implement a digital H-infinty robust controller for a MW-class PMSG-based grid-interactive wind energy conversion system Energies 6: 2084 2109

12 

Sanchis P, Ursaea A, Gubia E, Marroyo L (2005) Boost DC-AC inverter: A new control strategy IEEE Trans on Power Electronics 20: 2 343 353

13 

Aghatehrani R, Kavasseri R (2013) Sensitivity-analysis-based sliding mode control for voltage regulation in microgrids IEEE Trans on Sustainable Energy 4: 1 50 57

14 

Li SH, Zhou MM, Yu XH (2013) Design and implementation of terminal sliding mode control method for PMSM speed regulation system IEEE Trans on Industrial Informatics 9: 4 1879 1891

15 

Shtessel Y, Edwards C, Fridman L, Levant A (2014) Sliding mode control and observation Springer New York

Figures and Tables

Fig.1

Digitally controlled UPS inverter.

Digitally controlled UPS inverter.
Fig.2

Simulated waveforms of output voltage and the load current under (a) TRIAC load with the proposed control; (b) TRIAC load with classic SMC; (c) rectifier load with the proposed control; (d) rectifier load with classic SMC.

Simulated waveforms of output voltage and the load current under (a) TRIAC load with the proposed control; (b) TRIAC load with classic SMC; (c) rectifier load with the proposed control; (d) rectifier load with classic SMC.
Fig.3

Experimental waveforms of the output voltage and the load current under (a) TRIAC load with the proposed control. (b) TRIAC load with the classic SMC. (c) Rectifier load with the proposed control. (d) Rectifier load with the classic SMC.

Experimental waveforms of the output voltage and the load current under (a) TRIAC load with the proposed control. (b) TRIAC load with the classic SMC. (c) Rectifier load with the proposed control. (d) Rectifier load with the classic SMC.
Table 1

Fuzzy rule base

ifs-29-6-ifs1949-g004.jpg